1.Early resistance is low
2.High dust holding capacity
3.Compact structure
4.Easy to install
5.Economical and practical
Description
Features
Type | separated pleated cassette |
Frame | galvanized steel |
Filter media | glass fiber felt |
Protective Grids | galvanized steel mesh |
EN 779 Class | F5 |
Average arrestance | 94%(ASHRAE 52.1-1992) |
MERV | MERV 9(ASHRAE 52.2-1999) |
Final pressure drop | (recommender) 250Pa -(maximum)300Pa |
Max. air flow rate | 125% of nominal air flow rate |
Max. operating temperature | 280℃ |
Max. relative humidity | 80% |
Applications | fine particle filtration in ovens |
Specification
Type |
Class |
Arrestance |
Dimensions |
Filtering surface (m2) |
Rated air flow (m3/h) |
Initial pressure drop (Pa) |
||
Length (mm) |
Height (mm) |
Depth (mm) |
||||||
HTZ-55 |
F5 |
95% |
592 |
287 |
45 |
0.50 |
1700 |
90 |
HTZ-55 |
F5 |
95% |
592 |
592 |
45 |
1.10 |
3400 |
90 |
HTZ-55 |
F5 |
95% |
592 |
287 |
90 |
1.10 |
1700 |
100 |
HTZ-55 |
F5 |
95% |
592 |
592 |
90 |
2.30 |
3400 |
100 |